File:Sl silicone pipe covering.jpg

原始文件 (3,432 × 2,346像素,文件大小:771 KB,MIME类型:image/jpeg

摘要

描述 Mechanical pipe through-penetrations in 2 hour fire-resistance rated concrete floor slab with metallic piping, covered through the thickness of the firestops with 25mm thick rockwool pipe covering with foil scrim kraft facing. Running the pipe covering through the firestop maintains the vapour barrier. A weak link in the vapour barrier is the cutting and fitting required around riser clamps. Rockwool, foam glass, calcium silicate, perlite and vermiculite pipe covering can survive a fire test with a hose-stream. Foamed plastic, rubber and fibreglass require either removal or wrapping with an intumescent layer to be sure that as the pipe covering disappears during a fire, the vacated space is occupied by solid matter that can withstand the fire test and hose stream test, all subject to bounding.
日期
来源 自己的作品
作者 Achim Hering

许可协议

Public domain 本作品已被作者Achim Hering释出到公有领域。这适用于全世界。
在一些国家这可能不合法;如果是这样的话,那么:
Achim Hering无条件地授予任何人以任何目的使用本作品的权利,除非这些条件是法律规定所必需的。

说明

添加一行文字以描述该文件所表现的内容

此文件中描述的项目

描绘内容

创作作者 简体中文(已转写)

某些值没有维基数据项目

客体角色 简体中文(已转写):​摄影师 简体中文(已转写)
作者姓名字符串 简体中文(已转写):​Achim Hering
维基媒体用户名 简体中文(已转写):​Achim Hering

版权状态 简体中文(已转写)

文件来源 简体中文(已转写)

上传者的原创作品 简体中文(已转写)

文件历史

点击某个日期/时间查看对应时刻的文件。

日期/时间缩⁠略⁠图大小用户备注
当前2007年6月21日 (四) 02:322007年6月21日 (四) 02:32版本的缩略图3,432 × 2,346(771 KB)Achim Hering{{Information |Description=Mechanical pipe through-penetrations in 2 hour fire-resistance rated concrete floor slab with metallic piping, covered through the thickness of the firestops with 25mm thick rockwool pipe covering with foil scrim kra

全域文件用途

以下其他wiki使用此文件:

元数据