File:Sl silicone pipe covering.jpg

原始檔案 (3,432 × 2,346 像素,檔案大小:771 KB,MIME 類型:image/jpeg

摘要

描述 Mechanical pipe through-penetrations in 2 hour fire-resistance rated concrete floor slab with metallic piping, covered through the thickness of the firestops with 25mm thick rockwool pipe covering with foil scrim kraft facing. Running the pipe covering through the firestop maintains the vapour barrier. A weak link in the vapour barrier is the cutting and fitting required around riser clamps. Rockwool, foam glass, calcium silicate, perlite and vermiculite pipe covering can survive a fire test with a hose-stream. Foamed plastic, rubber and fibreglass require either removal or wrapping with an intumescent layer to be sure that as the pipe covering disappears during a fire, the vacated space is occupied by solid matter that can withstand the fire test and hose stream test, all subject to bounding.
日期
來源 自己的作品
作者 Achim Hering

授權條款

Public domain 此作品已由其作者,Achim Hering,釋出至公有領域。此授權條款在全世界均適用。
這可能在某些國家不合法,如果是的話:
Achim Hering授予任何人有權利使用此作品於任何用途,除受法律約束外,不受任何限制。

說明

添加單行說明來描述出檔案所代表的內容

在此檔案描寫的項目

描繪內容

檔案來源 Chinese (Taiwan) (已轉換拼寫)

檔案歷史

點選日期/時間以檢視該時間的檔案版本。

日期/時間縮⁠圖尺寸使用者備⁠註
目前2007年6月21日 (四) 02:32於 2007年6月21日 (四) 02:32 版本的縮圖3,432 × 2,346(771 KB)Achim Hering{{Information |Description=Mechanical pipe through-penetrations in 2 hour fire-resistance rated concrete floor slab with metallic piping, covered through the thickness of the firestops with 25mm thick rockwool pipe covering with foil scrim kra